volver

Addressable Dual Heat and Smoke Detector with Isolator

Referencia: DOTD-230A-I

Description

The new 200 series of analogue detectors has been developed using the most innovative technical advances. Its completely new design makes the 200 series one of the most elegant on the market, ideal for facilities in which the balance between functionality and aesthetics is necessary.

DETNOV's 200 range of analogue detectors is made up of 4 detector types. They are a 58ºC rise-of-rate detector, a 78ºC heat detector, an optical detector and an optical-heat detector. All of them are compatible with DETNOV's CAD-150 family of analogue control panels.

The 200 series of analogue detectors' addresses are assigned through the PGD-200 programmer. The use of this tool saves double address mistakes, because the programmer automatically handles the address to be assigned.

Connections between the analogue system's detectors and modules must be made with a 2 x 1.5 mm2 twisted and shielded cable with a maximum length of 2 Km. To meet the EN-54 requirements, the wiring must be done in a closed loop. Precise short-circuit isolators must be installed to facilitate the location of possible faults. The loop accepts up to 250 elements.

The DOTD-230A optical-heat detector is based in an optical dark chamber, which, thanks to its design, avoids unwanted air flows and facilitates the guidance of the smoke to the optical sensor. The detection principle is based on Tyndall's effect; the detector goes into alarm status due to the scattered light caused by the smoke particles being received by the optical sensor. The camera is protected to avoid the entrance of dirt and insects. This detector also incorporates compensation algorithms which avoid false alarms due to dirtiness of the optical chamber, postponing equipment maintenance.

The DOTD-230A high-heat detector also incorporates a temperature sensor that detects a quick temperature increase in a period of time, or a temperature higher than 58ºC.

In both the cases of detecting smoke and detecting heat, the heat detector will go into alarm state, and the detector's integrated LED will light up.

The 200 series detectors require the Z-200 base in order to connect. This connection base includes a blocking option which avoids it being tampered with. A tool is needed to remove the detector from the base.

Detectors in this series have non-polarity technology, facilitating system wiring and saving a huge amount of time in commissioning the system.

The protected area is 60 m2 and the maximum installation height is 12 meters.

The isolator  protects the system from short circuits in the loop, and its function is to disconnect the loop section between the 2 isolators that are nearest to the short circuit, allowing the rest of the installation to work without trouble. 

Features

     Elegant design and low profile
     Dirtiness compensation
     Dirtiness and insect protection
     Rise-of-rate function
     58ºC static alarm function
     Two-wire connection without polarity
     Compatible with DETNOV’s analogue fire control pane
     Addresses from 1 to 250 in the loop
     EN54-5, EN54-7 and EN54-17 approval

Aplications

DOTD-230A-I detectors are suitable for any fire-protected area, because its double technology (smoke & heat) can detect any kind of fire.

Technical features

Detector
Loop features:
   Operating voltage: From 22 to 38VDC
   Quiescent current consumption: < 300 μA
   Alarm current consumption: < 11 mA

Connections
2 x 1.5 mm2 twisted and shielded cable to Z-200 base

Environment
Operating temperature: From -10ºC to +70ºC
Relative humidity: 95% without condensation
IP Index: IP20

Physical features
Head (height x Ø): 48 mm x 100 mm
Base (height x Ø): 5 mm x 100 mm
Material: ABS

Approvals
EN54-5, EN54-7 and EN54-17
Certificate number: 0370-CPR-1862

Dimensions

Head (height x Ø): 48 mm x 100 mm
Base (height x Ø): 5 mm x 100 mm

Documents

You must be registered to access this section

DOTD-230A-I_0370-CPR-1862_EN.pdf

DXD-2XXA_Manual_ES_FR_EN_IT.pdf

DOTD-230A-I_01_Certificado_CE.pdf

DOTD-230A-I_14-0370-CPR-1862.pdf