Addressable Module 2 Technical Inputs

Referencia: MAD-402

Description

The range of MAD-400 modules has been developed to offer a wide and complete range of input and output ports to be used with Detnov's CAD-150 family of analogue fire control panels. These modules let you manage a wide variety of situations, by monitoring and acting according to the installation's requirements.

The MAD-400 modules have been designed to facilitate their installation process, and they may be installed using screws or fitted into a DIN rail. Each module is equipped with removable terminal blocks and a LED status indicator. The addressing of the modules is carried out through the PGD-200 programmer.

The MAD-401 and MAD-402 modules provide 1 and 2 logical inputs to the fire detection system, and are good for the supervision of any event that must be controlled (for example the opening or closing of doors, etc.). The MAD-401 and MAD-402 modules take the power supply directly from the loop.

Technical inputs can be configured through a micro-switch, depending on the signal type, to monitorize NC or NO input. There is also the option of configuring the supervision or non-supervision of the technical input.

Features

     Simple installation on the wall or fitted into a DIN rail
     Non-polarity supported
     Addressing through a programmer
     Stable communication protocol with immunity to noise
     Loop-powered device
     Connections through removable terminal blocks, and simple fitting of the cable
     EN54-18 approved

Aplications

The MAD-401 and MAD-402 modules are ideal for the supervision of any signal which may require control and supervision through a NC or NO contact (for example, the state of a door or a watertight door or the monitoring of any type of sensors which provide free contact relay).

Technical features

 

Module
Loop features:
   Operating voltage: From 22 to 38VDC
   Quiescent current consumption: < 300 μA
   Alarm current consumption: < 3 mA
Technical input through a NC or NO contact (configurable)

Connections
2 x 1.5 mm2 twisted and shielded cable

Environment
Operating temperature: From -10ºC to +70ºC
Relative humidity: 95% without condensation
IP Index: IP40

Physical features
Size: 100 mm x 82 mm x 23 mm
Size with removable terminal: 100 mm x 100 mm x 23 mm
Material: ABS

Approvals
EN54-18
Certificate number: 0370-CPD-1181

Dimensions

Size: 100 mm x 82 mm x 23 mm
Size with removable terminal: 100 mm x 100 mm x 23 mm