volver

Addressable Module 2 Conventional Zones

Referencia: MAD-442

Description

The range of MAD-400 modules has been developed to offer a wide and complete range of input and output ports to be used with Detnov's CAD-150 family of analogue fire control panels. These modules let you manage a wide variety of situations, by monitoring and acting according to the installation's requirements.

The MAD-400 modules have been designed to facilitate their installation process, and they may be installed using screws or fitted into a DIN rail. Each module is equipped with removable terminal blocks and a LED status indicator. The addressing of the modules is carried out through the PGD-200 programmer.

The MAD-441 and MAD-442 modules provide 1 and 2 conventional zones which support up to 20 conventional detectors and/or 32 conventional manual call points. The conventional zone monitor unit is able to distinguish between a detector alarm and a manual call point alarm.

The MAD-441 and MAD-442 modules require a 24V auxiliary power supply to supply the conventional detectors and the manual call point.

Features

     Simple installation on the wall or fitted into a DIN rail
     Non-polarity supported
     Addressing through a programmer
     Stable communication protocol with immunity to noise
     Requires an auxiliary 24V power supply
     Connections through removable terminal blocks, and simple fitting of the cable
     EN54-18 approved

Aplications

The MAD-441 and MAD-442 modules let you connect conventional detectors and conventional manual call points to the analogue system, and they are ideal for installations that, as a result of the area to be protected, require a large quantity of punctual detection elements that may all have the same identification (for example, car parks, corridors or open-plan areas). The use of conventional detectors will help reduce costs for the installation.

Technical features

Module
Loop features:
   Operating voltage: From 22 to 38VDC
   Quiescent current consumption: < 300 μA
   Alarm current consumption: < 3 mA
Auxiliary power supply features:
   Operating voltage: 24VDC
   Quiescent current consumption: < 5 mA
   Maximum alarm current consumption: 100 mA
Zone output features:
   Operating voltage: 24VDC
   QuQuiescent current consumption: < 5 mA
   Maximum current consumption: 100 mA

Connections
2 x 1.5 mm2 twisted and shielded cable
Environment
Operating temperature: From -10ºC to +70ºC
Relative humidity: 95% without condensation
IP Index: IP40

Physical features
Size: 100 mm x 82 mm x 23 mm
Size with removable terminal: 100 mm x 100 mm x 23 mm
Material: ABS

Approvals
EN54-18
Certificate number: 0370-CPD-1190

Dimensions

Size: 100 mm x 82 mm x 23 mm
Size with removable terminal: 100 mm x 100 mm x 23 mm

Documents

You must be registered to access this section

MAD-442_CPD-1190-EN.pdf

MAD-442_Manual_ES_FR_EN_IT.pdf

MAD-442_CE.pdf