volver

8 Zones ConventionalControl Panel

Referencia: CCD-108

Description

The CCD-100 fire control panels have been certified according to EN54-2 and EN54-4 standards, and they have been designed to meet all the requirements of small and medium installations.

This range of fire control panels is made up of 4 models, and it offers 2, 4, 8 and 12 zone models. Among the main features shared by the entire range: differentiation between the manual call point and detector alarm, free contact fault and alarm relay outputs, two supervised sounder outputs, 24V output, 24V resettable output and configurable input. The range also supports the connection of optional cards such as four free contact relays, four supervised output sounders and a communication card to control the system remotely.

Features

     2, 4, 8, and 12 zone models
     Free contact alarm relay output
     Free contact fault relay output
     2 supervised sounder outputs
     Sounder delay configuration on board
     24V auxiliary output
     24V resettable output
     Configurable external input
     Test mode with auto-reset function
     Multi-language keyboard
     Capacity for 72h stand-by batteries
     ABS plastic case which can be fitted into the wall
     Optional supervised sounder card
     Optional free contact relay card
     Optional communication card
     EN54-2 and EN54-4 approved

Aplications

The CCD-100 range of fire control panels are ideal products to meet all the requirements of small and medium installations. Thanks to their simplicity of installation and excellent quality-price ratio, these fire control panels are ideal for protected areas where up to 256 conventional fire detectors are required, such as shopping malls, schools, industrial buildings, car parks, etc.

Technical features

Control Panel
Power supply: 90 - 264VAC
Battery capacity: 2 x 2.3Ah / 2 x 7.5Ah
Zones:
   Max. alarm current consumption: 82 mA
   Max. quiescent current consumption: 3.5 mA
   Max. detectors per zone: 32
   Max. cable resistance per zone: 44 Ohms
Sounder output:
    Maximum load: 500 mA per output
    Delay configuration: from 0 to 10 minutes
Free contact relay output: 10A to 30VCC
24V auxiliary output: 500 mA
24V resettable output:
    Maximum load: 500 mA (2)
    Replacement time: 5 seconds
Environment
Operating temperature: From -5ºC to +40ºC
Relative humidity: 95% without condensation
IP Index: IP30

Physical features
Size: 443 mm x 268 mm x 109 mm
Size with packaging: 480 mm x 310 mm x 200 mm
Weight (without batteries): 1,9 Kg

Approvals
EN54-2 and EN54-4
Certificate number: 0370-CPD-0858

Dimensions

Size: 443 mm x 268 mm x 109 mm
Size with packaging: 480 mm x 310 mm x 200 mm

Documents

You must be registered to access this section

CCD-112_CPD-0858-EN.pdf

CCD-112_Manual_ES_FR_EN_IT.pdf

CCD-112_CE.pdf

CCD-112_09-0370-CPR-0858.pdf