Referencia: PCD-100
The PCD-100 is a manual call point for conventional detection systems. It is compatible with DETNOV’s conventional control panels and analog monitor units, and with the majority of the conventional panels in the market.
The resettable manual call point PCD-100 has been developed for using in conventional fire installations Once activated, it remains active until a manual reset is performed using the key.
The conventional manual call point PCD-100 is an essential element for the manual alarm generation in the conventional system. The manual call point is connected directly to the zone (It includes 100 Ohm 2W resistance for the alarm level in the conventional system).
■ Resettable manual call point
■ It includes a key for a maintenance test
■ Includes 100 Ohm 2W resistance for the alarm level
■ EN54-11 approved
The conventional manual call points are the elements used by the people to force the alarm state on the system.
Manual call point
Operating voltage: From 9 to 28VCC
Quiescent current consumption: < 100 μA
Alarm current consumption: < 100 mA
Connections
2 x 1.5 mm2 twisted and shielded cable to Z-200 base
Connections
Operating temperature: From -10ºC to +70ºC
Relative humidity: 95% without condensation
IP Index: IP40
Physical features
Size: 98 mm x 98 mm x 48 mm
Material: ABS
Approvals
EN54-11
Size: 98 mm x 98 mm x 48 mm