volver

Addressable Heat Detector with Isolator

Referencia: DTD-210A-I

Description

The new 200 series of analogue detectors has been developed using the most innovative technical advances. Its completely new design makes the 200 series one of the most elegant on the market, ideal for facilities in which the balance between functionality and aesthetics is necessary.

DETNOV's 200 range of analogue detectors is made up of 4 detector types. They are a 58ºC rise-of-rate detector, a 78ºC heat detector, an optical detector and an optical-heat detector. All of them are compatible with DETNOV's CAD-150 family of analogue control panels.

The 200 series of analogue detectors' addresses are assigned through the PGD-200 programmer. The use of this tool saves double address mistakes, because the programmer automatically handles the address to be assigned.

Connections between the analogue system's detectors and modules must be made with a 2 x 1.5 mm2 twisted and shielded cable with a maximum length of 2 Km. To meet the EN-54 requirements, the wiring must be done in a closed loop. Precise short-circuit isolators must be installed to facilitate the location of possible faults. The loop accepts up to 250 elements.

The DTD-210A-I rise-of-rate detector detects a quick temperature increase in a fixed period of time, or a temperature higher than 58ºC. In both cases the detector will go into alarm status, and the detector's integrated LED will light up. The temperature control is carried out through a thermistor which is controlled by a circuit, based on the most advanced technology.

The 200 series detectors require the Z-200 base in order to connect. This connection base includes a blocking option which avoids it being tampered with. A tool is needed to remove the detector from the base.

Detectors in this series have non-polarity technology, facilitating system wiring and saving a huge amount of time in commissioning the system.

The protected area is 20 m2 and the maximum installation height is 6 meters.

The isolator  protects the system from short circuits in the loop, and its function is to disconnect the loop section between the 2 isolators that are nearest to the short circuit, allowing the rest of the installation to work without trouble. 

Features

     Elegant design and low profile
     Heat and rise-of-rate function
     58ºC static alarm function
     Two-wire connection without polarity
     Remote indicator port
     Compatible with DETNOV’s analogue fire control panel
     EN54-5 and EN54-17 approved
     Addresses from 1 to 250 in the loop

Aplications

DTD-210A-I analogue detectors are suitable for those areas in a fire detection system in which a fire will cause more heat than smoke, and it is also suitable for those establishments where the daily activity produces smoke, steam or powder, such as industrial kitchens, boiler rooms, changing rooms and car parks.

Technical features

Detector
Power supply: 90 - 264VAC
Battery capacity: 2 x 7.5Ah
Loop features:
   Operating voltage: From 22 to 38VDC
   Quiescent current consumption: < 300 μA
   Alarm current consumption: < 11 mA

Connections
2 x 1.5 mm2 twisted and shielded cable to Z-200 base

Environment
Operating temperature: From -10ºC to +70ºC
Relative humidity: 95% without condensation
IP Index: IP20

Physical features
Head (height x Ø): 40 mm x 100 mm
Base (height x Ø): 5 mm x 100 mm
Material: ABS

Approvals
EN54-5 and EN54-17
Certificate number: 0370-CPR-1860

Dimensions

Head (height x Ø): 40 mm x 100 mm
Base (height x Ø): 5 mm x 100 mm

Documents

You must be registered to access this section

DTD-210A-I_0370-CPR-1860_EN.pdf

DXD-2XXA_Manual_ES_FR_EN_IT.pdf

DTD-210A-I_01_Certificado_CE.pdf

DTD-210A-I_14-0370-CPR-1860.pdf