volver

PCD-100 / Conventional Manual Call Point

Referencia: PCD-100

Description

The PCD-100 is a manual call point for conventional detection systems. It is compatible with DETNOV’s conventional control panels and analog monitor units, and with the majority of the conventional panels in the market.

The resettable manual call point PCD-100 has been developed for using in conventional fire installations Once activated, it remains active until a manual reset is performed using the key.

The conventional manual call point PCD-100 is an essential element for the manual alarm generation in the conventional system. The manual call point is connected directly to the zone (It includes 100 Ohm 2W resistance for the alarm level in the conventional system).

Features

     Resettable manual call point
     It includes a key for a maintenance test
     Includes 100 Ohm 2W resistance for the alarm level
     EN54-11 approved

Aplications

The conventional manual call points are the elements used by the people to force the alarm state on the system.

Technical features

Manual call point
Operating voltage: From 9 to 28VCC
Quiescent current consumption: < 100 μA
Alarm current consumption: < 100 mA

Connections
2 x 1.5 mm2 twisted and shielded cable to Z-200 base
Connections
Operating temperature: From -10ºC to +70ºC
Relative humidity: 95% without condensation
IP Index: IP40

Physical features
Size: 98 mm x 98 mm x 48 mm
Material: ABS

Approvals
EN54-11

Dimensions

Size: 98 mm x 98 mm x 48 mm

Documents

You must be registered to access this section

PCD-100_0370-CPR-2347_EN.pdf

PCD-100_Manual_ ES_FR_EN_IT.pdf

PCD-100_CE.pdf